CP12120 12V 12Ah(20hr)
Note: This battery is only available in New Zealand
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid
electrolyte is absorbed by separators and plates and thus immobilized. Should the
battery be accidentally overcharged producing hydrogen and oxygen, special oneway
valves allow the gases to escape thus avoiding excessive pressure build-up.
Otherwise, the battery is completely sealed and is, therefore, maintenance-free,
leak proof and usable in any position.
Battery Construction
Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid
General Features
l Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
l Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
l UL-recognized component.
l Can be mounted in any orientation.
l Computer designed lead, calcium tin alloy
grid for high power density.
l Long service life, float or cyclic
applications.
l Maintenance-free operation.
l Low self discharge.
Dimensions and Weight
Length(mm / inch) 151 / 5.94
Width(mm / inch) 98 / 3.86
Height(mm / inch) 95 / 3.74
Total Height(mm / inch) 101 / 3.98
Approx. Weight(Kg / lbs) 3.9 / 8.6
Performance Characteristics
Nominal Voltage 12V
Number of cell 6
Design Life 3~5 years
Nominal Capacity 77oF(25oC)
20 hour rate (0.6A, 10.5V) 12Ah
10 hour rate (1.14A, 10.5V) 11.4Ah
5 hour rate (2.05A, 10.5V) 10.25Ah
1 hour rate (8.14A, 9.6V) 8.14Ah
Internal Resistance
Fully Charged battery 77oF(25oC) 17mOhms
Self-Discharge
3% of capacity declined per month at 20oC(average)
Operating Temperature Range
Discharge -20~60oC
Charge -10~60oC
Storage -20~60oC
Max. Discharge Current 77oF(25oC) 180A(5s)
Short Circuit Current 600A
Charge Methods: Constant Voltage Charge 77oF(25oC)
Cycle use 14.5-14.9V
Maximum charging current 4.8A
Temperature compensation -30mV/oC
Standby use 13.6-13.8V
Temperature compensation -20mV/oC
Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell 5min 10min 15min 30min 1h 3h 5h 10h 20h
1.60V 46.4 31.7 24.8 13.8 8.14 3.18 2.12 1.18 0.61
1.65V 45.0 30.8 24.3 13.5 8.04 3.15 2.10 1.17 0.61
1.70V 43.5 29.9 23.7 13.3 7.94 3.12 2.07 1.16 0.61
1.75V 42.1 29.0 23.2 13.0 7.85 3.09 2.05 1.14 0.60
1.80V 40.6 28.2 22.6 12.7 7.75 3.06 2.02 1.12 0.59
|